Electrical Branch Circuit
Analyzers
| Product Name |
| Branch Circuit Standards | ||
| Description | Normal Range | Comments |
| Line Voltage | 108 132 | Low or high voltage will harm equipment. |
| % Voltage Drop@ 15 Amp. Load | <5.0% | NEC Part. 210-19, FPN 4. Excessive voltage drop can cause fires. (test for 15 amp. Circuit) |
| % Voltage Drop@ 20 Amp. Load | <5.0% | NEC Part. 210-19, FPN 4. Excessive voltage drop can cause fires. (test for 20 amp. Circuit) |
| Voltage between neutral and ground | < .5 Volts | Higher voltages upset microprocessor operation. Can often be noise. |
| Phase Conductor Impedance | <.25 Ohms | IEEE recommends less than .25 Ohms from any outlet to the building entry. |
| Neutral Conductor | <.25 Ohms | IEEE recommends less than .25 Ohms from any outlet to the building entry. |
| Ground Conductor Impedance | <.25 Ohms | IEEE recommends less than .25 Ohms. Critical for proper operation of surge protection devices. |