INTRODUCTION
Harmonix is a 3-phase 4-wire active harmonic filter.
Harmonix eliminates 100A rms of zero-sequence current
harmonics from the three phases and neutral conductor of
a 3-phase 4-wire distribution system with a high density
of non-linear electronic loads.

Fig. 1:
21"H x 24"W x 13"D, Floor
Mount Stackable INSTALLATION
THE
FOLLOWING IS INTENDED FOR QUALIFIED ELECTRICAL PERSONNEL
ONLY.
READ THE INSTALLATION INSTRUCTIONS COMPLETELY BEFORE
BEGINNING INSTALLATION. PLEASE CONTACT THE MANUFACTURER,
CURRENT TECHNOLOGY, WITH ANY QUESTIONS.
IT IS THE FINAL RESPONSIBILITY OF THE INSTALLING
ELECTRICIAN TO ENSURE THAT ALL LOCAL CODES AND OTHER
APPLICABLE SAFETY/ENVIRONMENTAL CONDITIONS ARE MET.
Enclosure/Environment: Current Technologys
Harmonix Active Harmonics Cancellation System is housed
in a NEMA Type 1 enclosure. The unit should be installed
in a safe, protected area with ambient temperature
between 0°C to +50°C (32°F to +132°F). The relative
humidity should be 5-95% non-condensing.
Verify Voltages: Ensure that ALL voltages are
correct and verify the type of power distribution
configuration used (i.e., 3 Phase 120/208 grounded WYE)
before installing the Harmonix. See Table 1 below for
nominal voltages.
Table 1
| |
Nominal
Voltages |
| Model
|
Voltage
|
Configuration
|
L-L
|
L-N
|
L-G
|
N-G
|
| HX3-100-120/208
|
120/208
|
Grounded
Wye |
208
|
120
|
120
|
-
|
Note: All
voltages should be within ± 10% of rated nominal
voltage.
WARRANTY VOID IF CONNECTED TO IMPROPER VOLTAGE. CHECK
SOURCE VOLTAGES BEFORE CONTINUING. CHECK NEUTRAL BOND AT
DISTRIBUTION TRANSFORMER PROVIDING POWER TO PROTECTED
LOADS AND NEUTRAL BOND AT SERVICE ENTRANCE TO VERIFY Xo
BOND CONNECTION INTEGRITY.
HARMONIX INSTALLATION
Location
- Install
Harmonix at the farthest downstream 3-phase
panelboard location possible within the
electrical distribution system.
- Install
Harmonix as close as possible to panelboards
feeding nonlinear electronic loads.
- Install
Harmonix in a location that reduces electrical
wire bends and wiring distances from the point of
connection to minimize installed system
impedance.
- Keep
conductor lengths as short as possible.
Mounting
Harmonix can
either be bolted on the floor or it can be mounted on the
wall (please see section on Mounting for details).
How to Connect the Harmonix Filter
Install Harmonix in parallel with the electrical
distribution system. Connect Harmonix to the
electrical distribution system via feed-through lugs in
the panelboard or via a 3-pole, 60A (max), UL Listed,
molded-case circuit breaker.
Safely perform the following power and control wire
connections:
Power Connections
- 5
power conductors will be utilized: 3 Phases, 1
Neutral, 1 Ground
- Phase
lugs: #14 2/0 AWG
- Neutral
lug: #4 500 MCM AWG
- Ground
lug: #14 2/0 AWG
Control
Connections
Connect the two control wires provided by Current
Technology from the neutral current monitoring
transformer to Harmonix. Because Harmonix is a
closed-loop control filter, it is critical to correctly
install the neutral current monitoring transformer
correctly in the panelboard (please see section on
"Installation of Neutral Conductor CT" for
details).
Table 2:
Recommended
Single Unit Wire Size
| Conductor
Wire |
Phase
Lug Size |
Minimum
Recommended Wire Size |
| Phase
Wires ABC |
#142/0 |
#6
AWG 75oC Class THHW or THWN Insulation
OR #8 AWG 90oC Class THHN Insulation |
| Neutral
Conductor |
#4500
MCM |
#1
AWG 75oC Class THHW or THWN Insulation
OR #2 AWG 90oC Class THHN Insulation |
| Ground
Conductor |
#142/0 |
#8
AWG 75oC Class THHW or THWN |
Table 3:
Recommended Wire Size for Two Units in Parallel
| Conductor
Wire |
Phase
Lug Size |
Minimum
Recommended Wire Size |
| Phase
Wires ABC |
#142/0 |
#1
AWG 75oC Class THHW or THWN Insulation
OR #2 AWG 90oC Class THHN Insulation |
| Neutral
Conductor |
#4500
MCM |
300
MCM 75oC Class THHW or THWN Insulation
OR 250 MCM 90oC Class THHN Insulation |
| Ground
Conductor |
#14
2/0 |
#8
AWG 75oC Class THHW or THWN |
Conduit
Hole Location
Figures 24 show the three possible conduit entry
locations. Select the location yielding the shortest
possible conductor lengths. Punch the conduit hole for
the conduit connector (maximum conduit diameter =
3.00") in the shaded areas shown in Figures
24. These locations ensure that external wiring
will not interfere with internal components or require
sharp bends. Do not use the hole provided in the top for
conduit entry. This hole is reserved for stacking
multiple Harmonix units in parallel.
Maximum Conduit Hole Size: 3" Diameter 
Fig. 2:
Side View (Left) Harmonix Filter
Fig. 3:
Side View (Right), Harmonix Filter

Fig. 2:
Top View, Harmonix Filter Electrical
Connection
Install
Harmonix in parallel with the electrical power
distribution system via feed through lugs or a 3-pole,
60A (max), UL listed molded-case circuit breaker. After
selecting the conduit entry location for Harmonix,
establish an opening through the metal cabinet and run
required length of the phase, neutral and ground wires
through the conduit. NOTE: Also run the neutral current
monitoring transformer wires through the conduit. Connect
phases A, B, and C conductors to the phase terminal
block, then connect the neutral conductor to the neutral
terminal block mounted on the inner back wall of the
filter (Figures 67) before connecting the ground
wire to the equipment ground terminal. Connect the black
wire of the neutral current monitoring transformer to the
control terminal block, pin 7 and the white wire to pin 9
of the control terminal block (Figure 8 and Table 4).
Remote Monitor Contacts Option
- All
Harmonix models include two sets of form
"C" monitor dry contacts that may be
connected to the building management system or
remote annunciation alarm panels.
- When
dry contacts wiring is routed in the same conduit
as the phase wiring and the neutral wiring, use
NEC Class 1 wiring method.
- Dry
contact ratings must not exceed the Class 2
limit.
- Figure
8 shows the control terminal block and the form
"C" remote monitoring contact output.
Each set of contacts may be wired independently.
- Each
set of form "C" remote monitoring
contacts include common (C), normally open (NO)
and normally closed (NC) contacts. For normally
open operation under energized conditions,
connect the normally open terminals and common
terminal to the monitoring input. For normally
closed operation during energized conditions,
connect the normally closed terminal and common
terminal to the monitoring input. The contacts
change to the Alarm State during malfunction of
Harmonix or loss of power.

Fig. 6: Internal View - Harmonix Filter
Conduit and Wire Entry from Left side of the Enclosure

Fig. 7: Internal
View - Harmonix Filter
Conduit Entry from Right or Back Side of the Filter

Fig. 8:
Control Terminal Block, Harmonix Filter
Table 4
| Terminal
Block Number |
Terminal
Block Connection |
Application
|
| 1 |
NO1 |
2
Form C Dry Contacts |
| 2 |
C1 |
2
Form C Dry Contacts |
| 3 |
NC1 |
2
Form C Dry Contacts |
| 4 |
NO2 |
2
Form C Dry Contacts |
| 5 |
C2 |
2
Form C Dry Contacts |
| 6 |
NC2 |
2
Form C Dry Contacts |
| 7 |
Neutral
Current |
Black
Wire
(from Current Transformer) |
| 8 |
Neutral
Current |
White
Wire
(from Current Transformer) |
| 9 |
Load
Share Current |
For
2nd Unit in Parallel
(see Multiple Unit section) |
| 10 |
Load
Share Current |
For
2nd Unit in Parallel
(see Multiple Unit section) |
| 11 |
Filter
Current |
Pre-connected
by Factory
(Black Wire) |
| 12 |
Filter
Current |
Pre-connected
by Factory
(White Wire) |
Connection
to the Distribution Panel Board
- Ensure
that the breaker supplying power to the
panelboard is de-energized.
- Turn
Harmonix breaker to the OFF position
- Turn
Harmonix filter control panel switch to the OFF
position
- Harmonix
is connected in parallel with the 3-phase 4-wire
distribution system as shown in Figures
1112. Figure 11 depicts the installation of
the Harmonix filter via feed-through lugs. Figure
12 shows the connection of the filter to the
system using a 3-pole, 60A, UL listed molded-case
circuit breaker. Before connecting Harmonix,
ensure that the panelboard is completely
de-energized. Insert the neutral current
monitoring current sensor in the incoming neutral
wire in the proper direction as shown in Figure 9
and 10 and discussed in the next two sections.
Installation
of Neutral Conductor Monitoring Transformer (Standard CT)
- Ensure
that the breaker supplying power to the
panelboard is de-energized.
- Unscrew
the incoming neutral conductor of the panelboard
and insert the neutral current monitoring (CT)
into the neutral conductor with "HI",
"XI" and "500:5" pointing to
the line-side or towards the service entrance.
Return the neutral conductor back to its normal
position (please see Figure 9).
- Secure
the secondary wiring of the CT away from all
phase and neutral conductor components. Ensure
that this wiring is not in contact with any sharp
edges of the panelboard.
- Route
the secondary wiring of the CT in the same
conduit as the phase, neutral and ground
conductors.
Installation
of Neutral conductor Monitoring Transformer (Split-Core
CT)
- Ensure
that the breaker supplying power to the
panelboard is de-energized
- Unscrew
the split-core neutral current monitoring
transformer and wrap it around the incoming
neutral conductor of the panelboard with arrow
pointing to the line-side or towards the service
entrance (please see Figure 10).
- Secure
the secondary wiring of the CT away from all
phase and neutral conductor components. Ensure
that this wiring is not in contact with any sharp
edges of the panelboard.
- Route
the secondary wiring of the CT in the same
conduit as the phase, neutral and ground
conductors.

Fig. 9: Installation of Neutral Current Monitoring
Current Transformer (Standard CT)
|