EGPE65 Electronic Grade
Panelboard Extension
Technical Specifications Easily mounts with most major brands of non-linear, six-wire panelboards – compatible with all Current Technology MasterPLAN suppression filter systems
FEATURES
No other manufacturer comes close to the innovative, cost effective and practical electronic panelboard alternatives offered by Current Technology. Logical EGPE Panelboard Extensions permit the quick and easy addition of Current Technology's UL 1449 Listed suppression and UL 1283 Listed filtering to electric panelboards at the jobsite. Mounted at the top, bottom or adjacent to virtually any panelboard, EGPE Panelboard Extensions include the following standard features:

seamless technology: Proprietary design concept integrates three key suppression and filtering components – polypropylene capacitors, non-linear voltage dependent metal oxide varistors (MOVs) and precise component geometry – for maximum performance and reliability

Superior internal construction: All suppression filter components are bolted to corrosion-resistant tin-plated copper bus bar

Status indicators: Neon status indicators indicate suppression and overcurrent status

Test point: Diagnostic ten mode test point allows easy DTS-2 Diagnostic Test Set connection

Warranty: Five Year Product Warranty

INDUSTRY STANDARDS CERTIFICATION

standard

description

UL 1449

Underwriters Laboratories standard that establishes requirements for surge suppression safety and performance. Commonly recognized as a benchmark test for product comparison

UL 1283

Underwriters Laboratories standard dictating requirements for electromagnetic interference (EMI) filters installed on, or connected to, 600V or lower potential circuits installed in accordance with the National Electrical Code. Also covers filters used to attenuate unwanted high frequency signals generated from electromagnetic sources

CUL

Canadian version of Underwriters Laboratories

NEMA LS-1

The specification format guideline published by the National Electrical Manufacturers Association for specifiers and customers investigating Low Voltage Surge Protection Devices
STANDARD MODEL NUMBERS
EGPE65-120/240-2G-F or S EGPE65-120/240-3GHD-F or S
EGPE65-120/208-3GY-F or S EGPE65-240-3D-F or S
EGPE65-277/480-3GY-F or S EGPE65-480-3D-F or S
EGPE65-347/600-3GY-F or S EGPE65-600-3D-F or S

Contact factory for other voltages and configurations. Add F for Flush mount or S for Surface mount plus option suffix(es).

SINGLE PULSE SURGE CURRENT CAPACITY

Protection mode

Single pulse surge current
capacity per mode

Line-to-Neutral

>65,000 amps

Line-to-Ground

>65,000 amps

Neutral-to-Ground

>65,000 amps

Line-to-Line

>65,000 amps

Per Phase

>130,000 amps

In compliance with NEMA LS 1-1992, paragraphs 2.2.7, 2.2.9 and 3.9, Current Technology suppression filter systems are single pulse surge current tested in all modes at currents up to 150% of the product design rating by an industry-recognized independent test laboratory. Single pulse surge current capacities of 200,000 amps or less are established by single-unit testing of all components within each mode. Due to present industry test equipment limitations, single pulse surge current capacities over 200,000 amps are established via testing of individual components or sub-assemblies within a mode.

REPETITIVE SURGE CURRENT CAPACITY

Protection mode

Minimum tested impulses per mode

Line-to-Neutral

>3,500

Line-to-Ground

>3,500

Neutral-to-Ground

>3,500

Line-to-Line

>3,500

Per ANSI/IEEE C62.41-1991 and ANSI/IEEE C62.45-1992, all Current Technology suppression filter systems are repetitive surge current capacity tested in every mode utilizing a 1.2 X 50m sec 20KV open circuit voltage, 8 X 20 m sec 10 KA short circuit current Category C3 bi-wave at one minute internals without suffering either performance degradation or more than 10% deviation of clamping voltage at a specified surge current.

EMI/RFI NOISE REDUCTION VALUES

Multiple unit installation

Frequency

Single unit installation

51 dB

100 KHz

34 dB

94 dB

1 MHz

51 dB

114 dB

10 MHz

54 dB

120 dB

100 MHz

48 dB

All Current Technology suppression filter systems EMI-RFI noise rejection or attenuation values are in compliance with test and evaluation procedures outlined in NEMA LS 1-1992, paragraphs 2.2.11 and 3.11.

MAXIMUM CONTINUOUS OPERATING VOLTAGE (MOV)

Voltage MCOV

Voltage MCOV

120V 150V

277V 320V

240V 275V

480V 600V

277V 320V

600V 840V

All Current Technology suppression filter systems maximum continuous operating voltages are in compliance with test and evaluation procedures outlined in NEMA L 1-1992, paragraphs 2.2.6 and 3.6.

TYPICAL VOLTAGE CLAMPING DATA

Voltage

Protection Mode

A3 Ringwave

B3 Ringwave

B3/C1 Comb. Wave

C3 Comb. Wave

120/208

L-N

210

260

380

480

120/208

L-G

350

365

370

540

120/208

N-G

250

290

360

520

120/208

L-L

360

480

700

810

277/480

L-N

460

580

835

980

277/480

L-G

800

755

765

990

277/480

N-G

500

570

785

1050

277/480

L-L

805

1040

1555

1780

All Current Technology suppression filter systems clamping voltages are in compliance with test and evaluation procedures outlined in NEMA LS 1-1992, paragraphs 2.210 and 3.10. Values indicate typical clamping voltage data for models with integral fused disconnect (DF).

MECHANICAL SPECIFICATIONS
Connection method Parallel
Enclosure type/mount NEMA 1/surface or flush
Temperature operating range -40C to 60C
Humidity operating range 5% - 95% non-condensing
Dimensions 12.00"Hx20.00"Wx5.75"D
Weight 35 lbs.
OPTIONS

Option

Order Suffix

Double form "C" dry contacts -FCC
StatusWatch diagnostic monitoring -SW
StatusWatch with display event counters -SWC
DTS-2 Diagnostic Test Set -DTS
Remote StatusWatch -RSW
Remote StatusWatch with counters -RSWC
Remote Alarm Panel (monitors 1 unit) -RAP1
Remote Alarm Panel (monitors 1-5 units) -RAP5
Remote Alarm Panel (monitors 1-12 units) -RAP12
All StatusWatch diagnostic monitoring options include double form "C" dry contacts, audible alarm, alarm silence/test and status indicator lights.
Ask an Engineer if you have any questions regarding this or other Current Technology products.

BACK

For more information about these or any other surge protection products or to speak with one of our sales reps, please contact us.

Tel: 407-380-9200 Fax: 407-380-3911 Email: jwest@psihq.com

About PSI Services Products Informational Readings Companies we Represent Business Opportunities Employment Opportunities Links


Copyright 1999 Current Technology. All Rights Reserved.