TransEnd™ surge protectors combine practicality with many special features to deliver more performance than any other device in its class. Designed to meet demanding project requirements, TransEnd is the right choice for today’s competitive environment. These MOV-based protectors are available in all standard low-voltage AC configurations with surge current capacities ranging from 25 kA to 100 kA.

Sensitive electrical and electronic equipment requires clean power and protection against lightning damage and surge-induced degradation. TransEnd delivers just that. These MOV-based protectors are available in all standard low-voltage AC configurations with surge current capacities ranging from 25 kA to 100 kA. From manufacturing plants, commercial buildings and military installations to hospitals, data centers, and telecommunications operations, TransEnd cost-effectively satisfies the protection requirements of all types of facilities.

Immediate shipment! Featuring 25kA, 50kA, 80kA and 100kA models

· Protects facilities and equipment against catastrophic lightning strikes and internally generated electrical transients

· Tested single-pulse surge current capacity per NEMA 2.2.9 and 3.9 recommendations

· Comes with pre-wired pigtail terminals to streamline installation

· Features arc-quenching, sand-packed design

· Backed by certified, independent laboratory performance test reports

· 3-day or less delivery

Proven technology: TransEnd delivers worry-free performance in a reliable, innovative design. The tested single-pulse surge current capacity (per mode) is tested per NEMA recommendations. Sand-packed MOV arrays equally share current to suppress transients before they reach sensitive loads while capacitors filter out high-frequency noise and low-level transients. TransEnd is designed and tested to withstand surge currents in accordance with ANSI/IEEE recommendations.

Instantaneous protection: TransEnd responds immediately and reliably to repeated high-current lightning incidents and other transient voltage surges. All TransEnd models are designed to exceed the minimum performance criteria of Bellcore and withstand larger impulses referenced in IEEE.

Superior internal construction: TransEnd’s innovative design ensures dependable operation. The suppression filter components are bolted directly to copper bus bars, lowering system impedance and clamping voltage and increasing reliability.

Status indicators: LEDs for each phase illuminate to clearly indicate protection is active.

Prewired: For ease of installation, TransEnd is equipped with 24-inch, stranded #10 AWG pigtail conductors. The conductors can be cut to fit the application and to permit the shortest connection for optimum performance.

Flex Conduit: For easy field installation, TransEnd is factory-equipped with a flexible conduit and a versatile ¾-inch-diameter fitting, allowing the installer to use either flex or conduit.

Rugged, Compact Enclosure: Measuring only 7"W x 7"H x 5"D, TransEnd easily installs in tight spaces. The NEMA 4 fiberglass-reinforced plastic (FRP) housing features a nonremovable cover for protection against tampering.

Warranty: Five-Year Product Warranty

New from the pioneer in AC surge protection, the Joslyn® TransEnd™ has everything you look for in a small, powerful surge protection device.

Versatility. Reliability. Value.
TransEnd combines practicality with many special features to deliver more performance than any other device in its class. Designed to meet demanding project requirements, TransEnd is the right choice for today's competitive environment.

Sensitive electrical and electronic equipment requires clean power and protection against lightning damage and surge-induced degradation. TransEnd delivers just that. These MOV-based protectors are available in all standard low-voltage AC configurations with surge current capacities ranging from 25 kA to 100 kA. From manufacturing plants, commercial buildings and military installations to hospitals, data centers, and telecommunications operations, TransEnd cost-effectively satisfies the protection requirements of all types of facilities.

Put Joslyn technical expertise to work for you
You can look to our Applications Engineering staff for help in choosing the TransEnd units for your specific applications and requirements. To assist you in total power systems engineering, Joslyn maintains professional alliances with major switchgear, power cabinet and electronic equipment manufacturers, as well as electrical and grounding advisory firms. We will coordinate integration of equipment offerings and engineering services to ensure value-based solutions consistent with sound engineering practices.

Communications system and point-of-use protection
Voice/data communications lines are highly susceptible to lightning and transients that cause errors or loss of transmitted data. Our communications protection devices maximize the uptime and reliability of telephone, fax, modem and dial-up lines; communications servers; and satellite communications, cable television and networked systems. Point-of-use protection for AC power applications is the job our hard-wired, series-connected LoadGuard™ unit handles with ease. For more details, refer to page X.


"24x7" installation hotline
TransEnd users have access to a dedicated, toll-free "24x7" hotline. You can access our professional field service engineers by dialing:

888-200-6400 Nights, weekends and holidays
800-238-5000 Monday through Friday, 8:00 a.m. - 5:00 p.m. (CST)

TransEnd: Easy to specify. Easy to install.
Tested Single-Pulse Surge Current Capacity (per mode):
TransEnd 100: 100kA
TransEnd 80: 80kA
TransEnd 50: 50kA
TransEnd 25: 25Ka

Responsive Customer Service
To place orders or inquire about product pricing, availability or order status, please contact Joslyn Customer Service. Our professional staff of representatives is available to assist you from 6:00 a.m. to 5:00 p.m. (Pacific), Monday through Friday. When you require technical support, your call will be directed immediately to our Applications Engineering team.



Frequency

Model XN25-100 (L-N)

Model XN25-100 (L-N)

6-in. Hook-Up Wire
50-ft. Noise Source

6-in. Hook-Up Wire
100-ft. Noise Source

db

db

100kHz

-50

-50

1MHz

-34

-39

10MHz

-34

-40

100MHz

-47

-53


standard

description

UL 1449

Underwriters Laboratories standard that establishes requirements for surge suppression safety and performance. Commonly recognized as a benchmark test for product comparison

UL 1283

Underwriters Laboratories standard dictating requirements for electromagnetic interference (EMI) filters installed on, or connected to, 600V or lower potential circuits installed in accordance with the National Electrical Code. Also covers filters used to attenuate unwanted high frequency signals generated from electromagnetic sources

CUL

Canadian version of Underwriters Laboratories

NEMA LS-1

The specification format guideline published by the National Electrical Manufacturers Association for specifiers and customers investigating Low Voltage Surge Protection Devices

6kV / 500A combination waveform


system voltage


MODEL NO.

PROTECTION MODES


L-N


L-G


N-G


L-L


120/208

XN100-120/208-3GY

391

391

388

735

XN80-120/208-3GY

391

391

388

735

XN50-120/208-3GY

391

391

388

735

XN25-120/208-3GY

408

397

392

784


277/480

XN100-277/480-3GY

890

868

820

1665

XN50-277/480-3GY

890

868

820

1665

XN80-277/480-3GY

890

868

820

1665

XN25-277/480-3GY

890

868

820

1665

Modes of Protection: L-N, L-G, N-G, L-L EMI/RFI
Noise Rejection: Filtering Attenuation Frequencies

Method of Operation
When a transient surge exceeds the normal system voltage, TransEnd responds within nanoseconds and changes state from a high-impedance open circuit to a low-impedance shunt (short circuit). Connected in parallel with the facility’s loads, TransEnd diverts damaging current away from sensitive loads while simultaneously reducing (clamping) the high transient voltage to harmless levels. Upon the end of the transient event, TransEnd automatically returns to its normal operating condition without service interruption.

Applicable approvals and standards
UL 1449, 2nd Edition: Underwriters Laboratories standard that establishes requirements for surge suppression safety.

CUL: Canada Underwriters Laboratories standard that establishes requirements for surge suppression safety.

UL 1283: Underwriters Laboratories standard specifying requirements for electromagnetic interference (EMI) filters permanently installed in systems of 600V or less. The requirements also cover filters used to attenuate unwanted radio frequency interference (RFI) generated by electromagnetic sources.

NEMA LS-1: The specification format guideline published by the National Electrical Manufacturers Association for specifiers and customers investigating Low-Voltage Surge Protection Devices.

ANSI/IEEE C62.41: IEEE Recommended Practice on Surge Voltages in Low-Voltage AC Power Circuits

ANSI/IEEE C62.45: IEEE Guide on Surge Testing for Equipment Connected to Low-Voltage AC Power Circuits.

ANSI/IEEE C62.1: IEEE Standard for Gapped Silicon-Carbide Surge Arresters for AC Power Circuits

ANSI/IEEE C62.11: IEEE Standard for Metal-Oxide Surge Arresters for Alternating Current Power Circuits

Critical considerations when selecting surge protection devices
Two primary factors influence the minimum life expectancy of a surge protection device: the frequency and the intensity of surge-causing events (for example, lightning- induced surges, power factor correction capacitor and load switching). For optimum protection, it is imperative to properly select the device appropriate for the following factors:

    1. the facility’s exposure to surges (rather than to the size of the load or service);
    2. the criticality or value of the equipment being protected;
    3. the location of the surge protection device within the facility’s power distribution system; and
    4. the level of power disturbances generated by the facility’s electrical and electronic equipment.

Based on your project and protection requirements, we can help you determine which devices and installation locations will best achieve your objectives.

Standard Model Numbers

TransEnd 25
XN25-120/240-2G, XN25-120/208-3GY, XN25-220/380-3GY, XN25-277/480-3GY, XN25-347/600-3GY, XN25-120/240-3GHD, XN25-240-3DG, XN25-380-3DG, XN25-480-3DG, XN25-600-3DG

TransEnd 50
XN50-120/240-2G, XN50-120/208-3GY, XN50-220/380-3GY, XN50-277/480-3GY, XN50-347/600-3GY, XN50-120/240-3GHD, XN50-240-3DG, XN50-380-3DG, XN50-480-3DG, XN50-600-3DG

TransEnd 80
XN80-120/240-2G, XN80-120/208-3GY, XN80-220/380-3GY, XN80-277/480-3GY, XN80-347/600-3GY, XN80-120/240-3GHD, XN80-240-3DG, XN80-380-3DG, XN80-480-3DG, XN80-600-3DG

TransEnd 100
XN100-120/240-2G, XN100-120/208-3GY, XN100-220/3100-3GY, XN100-277/4100-3GY, XN100-347/600-3GY, XN100-120/240-3GHD, XN100-240-3DG, XN100-3100-3DG, XN100-4100-3DG, XN100-600-3DG

5-Year Product Warranty

Options

Dry Contacts
Single Form "C" dry contacts for remote alarm monitoring are available as an option. To order a model with dry contacts, add suffix "-FCC" to the standard part number. Example: XN100-120/208-3GY-FCC

Fittings
Option A: Metallic conduit installation kit has a ¾" x 3" metallic nipple and all associated hardware required to compelte the TransEnd installation. Part No. 300-0155-001

Option B: Flexible plastic conduit installation kit, including 18" flexible conduit and all associated hardware required to complete the TransEnd installation.

Specifications
Dimensions: 7"H x 7"W x 5"D

Weight (all models): 12.7 lbs.

Enclosure Type: NEMA 4, surface-mount

Operating Environment: -40oC to +60oC, 5% to 95% noncondensing humidity

Connection Method: Parallel

Protection Modes: L-N, L-G, N-G, L-L

Ask an Engineer if you have any questions regarding this or other Current Technology products.

BACK

For more information about these or any other surge protection products or to speak with one of our sales reps, please contact us.

Tel: 407-380-9200 Fax: 407-380-3911 Email: jwest@psihq.com

About PSI · Services · Products · Informational Readings · Companies we Represent · Business Opportunities · Employment Opportunities · Links


© Copyright 1999 Current Technology. All Rights Reserved.